Home / Products / Industrial Power Supply

PP-250-24
PP-250-24

Model:PP-250-24

Vertical multifunctional distributed

Rail-type industrial power supply, 250W single output with PFC function

Our Advantages

Customized industrial bus technology product solutions and related technical service

Key performance indicators are benchmarked against international brands such as Siemens and Beckhoff

With 20 years of experience, we have successfully served more than 1,000 customers in the fields of photovoltaics, lithium batteries, semiconductors, etc.

Product Details

Resource Download

Resource Download

Do you have any questions about our products? Contact our experts

Product Parameters

Product Parameters

Order Number: PP-250-24

● Full range AC input: 90~264VAC

● Built-in active PFC function

● Protection types: Short circuit/Overload/Overvoltage/Overtemperature

● Mounting rail: TS-35/7.5 or 15

● Narrow width: 50mm

● 100% full load aging test

● Power-on LED indicator

● DC OK relay contact (optional)

● High efficiency/High reliability

● 3-year warranty

● Compliant with IEC/EN/UL 62368-1

Input Parameters

Voltage Range: 90 - 264VAC, 127 - 370VDC

Frequency Range: 47 - 63Hz

Efficiency (Typical): 93%

AC Current (Typical): 3A/115VAC, 1.5A/230VAC

Inrush Current (Typical): 20A/115VAC, 40A/230VAC (Cold Start)

Leakage Current: < 2mA/240VAC

Output parameters:

DC Voltage: 24V

Rated Current: 10.4A

Current Range: 0 - 10.4A

Rated Power: 249.6W

Ripple and Noise (Maximum): 150mVp-p

Voltage Adjustment Range: 24 - 28V

Voltage Accuracy: ±1%

Line Regulation: ±0.5%

Load Regulation: ±1%

Startup, Rise Time: 1500ms, 50ms/230VAC 3000ms, 50ms/115VAC

Hold Time (Typical): 4ms/230VAC 14ms/115VAC

Protection parameters:

Overload: 105% to 135% of rated output power

Protection mode: Constant current limit (output voltage > 50% Vo), otherwise hiccup, self-recovery after abnormal condition removed

Overvoltage: 29 to 33V

Protection mode: Shutdown, recovery after restart

Overtemperature:

Protection mode: Shutdown, recovery after restart

Environmental parameters:

Operating temperature and humidity: -20 to +70℃ (refer to "derating curve"), 20 to 90% RH, no condensation

Storage temperature and humidity: -40 to +85℃, 10 to 95% RH

Temperature coefficient: ±0.03%/℃ (0 to 50℃)

Vibration resistance: 10 to 500Hz, 2G for 10 minutes per cycle, along X, Y, and Z axes respectively


Do you have any questions about our products? Contact our experts